Na partida do equipamento, a válvula do elemento-x fica na posição aberta e grandes quantidades de ar são descarregadas rapidamente, reduzindo muito o tempo de partida do equipamento. Quando começa a entrada do vapor, a válvula do elemento-x se fecha imediatamente. A válvula permanece fechada enquanto a temperatura ao seu redor esteja próxima à temperatura de saturação. Como a entrada de ar faz com que a temperatura caia, a válvula será novamente aberta e o ar será descarregado rapidamente.